Knowledge article · Pillar
What Is an EICR? A Complete Guide
An EICR (Electrical Installation Condition Report) is a formal assessment of a fixed electrical installation's safety against BS 7671.
An Electrical Installation Condition Report (EICR) is a formal document produced after a periodic inspection and test of a building's fixed electrical installation. It records the condition of the installation against the requirements of BS 7671 (the IET Wiring Regulations) and identifies anything that is unsafe, deteriorating, or does not meet current standards.
The EICR looks at the fixed installation — consumer units (fuse boards), wiring, accessories, protective devices, earthing and bonding — not portable appliances, which are covered separately by in-service inspection and testing (often called PAT).
What an EICR actually checks
During the inspection a competent person examines and tests the installation for:
- Safety — adequacy of earthing and bonding, and protection against electric shock.
- Damage and deterioration — cabling, enclosures and accessories that have degraded or been damaged.
- Overload and fault protection — that protective devices are correctly rated and will disconnect within required times.
- Non-compliance with BS 7671 — installation methods that no longer meet the current edition of the Wiring Regulations.
- Conditions that may cause danger — such as the absence of RCD protection where it is now required.
Legislation, standards and guidance
It is important to distinguish the three things an EICR touches:
- Legislation is the law — for example the Electricity at Work Regulations 1989 and, for rented homes in England, the Electrical Safety Standards in the Private Rented Sector (England) Regulations 2020.
- BS 7671 is a standard — the recognised benchmark for a safe installation. It is not law in itself, but compliance with it is the accepted way of meeting the legal duty to maintain a safe installation.
- Guidance includes IET Guidance Notes and Codes of Practice that explain how to apply the standard in practice.
Understanding the result
An EICR is reported as either Satisfactory or Unsatisfactory. Observations are classified with codes:
- C1 — Danger present. Risk of injury; immediate action required.
- C2 — Potentially dangerous. Urgent remedial action required.
- C3 — Improvement recommended. Not dangerous, and does not by itself make a report unsatisfactory.
- FI — Further investigation required without delay.
Any C1, C2 or FI makes an installation Unsatisfactory. A report with only C3 items is still Satisfactory.
What happens next
Where an EICR is unsatisfactory, the recorded C1, C2 and FI items should be remediated by a competent person and the work certified. For rented homes in England there are specific timescales for completing remedial work and supplying evidence to the tenant and local authority.
An EICR gives duty holders — landlords, employers, facilities managers and property owners — documented assurance that their installation is safe, and a clear, prioritised list of any work needed to keep it that way.
Frequently asked questions
Is an EICR a legal requirement?
For rented homes in England an EICR is a legal requirement under the Electrical Safety Standards in the Private Rented Sector (England) Regulations 2020. For commercial premises there is no single law naming the EICR, but duties under the Electricity at Work Regulations 1989 and the Health and Safety at Work etc. Act 1974 make periodic inspection and testing the recognised way to demonstrate a safe installation.
Who can carry out an EICR?
An EICR must be carried out by a competent person — typically a qualified electrician or approved contractor with current knowledge of BS 7671 and the appropriate test instruments and inspection experience for the type of installation.
More in this topic
Knowledge article
What Affects the Cost of an EICR?
The cost of an EICR depends on the number of circuits, the size and type of premises, access, and the age and condition of the installation.
Learn moreKnowledge article
How Often Is an EICR Required?
How often an EICR is required depends on the type of premises and its use — from every 5 years for rented homes to risk-based intervals commercially.
Learn moreKnowledge article
What Happens During an EICR?
During an EICR a competent person carries out a visual inspection and a series of dead and live tests on the fixed installation, then reports the results.
Learn moreThis article provides general guidance and distinguishes legislation, British Standards and good practice. It is not legal advice. Always confirm the specific duties applying to your property and tenure.